Technical data
PRS 50 cycling timer
Indicators and controls
– 1 x green 4-digit, 7-segment display for showing status information
– 3 x LEDs (2 x yellow, 1 x red)
– 1 x 4-pole code switch for con guration (standby/burner function)
– 1 x rotary knob with integrated push-button for setting parameters and executing the test function
Supply voltage
24 V DC +/-20 % (external fuse M 0.5 A)
Protection class
II double insulated
Admissible ambient temperature
0 °C to 55 °C
Weight
Approx. 0.2 kg
2/3-way solenoid valve 6430 C
Mechanical connection
G 1⁄4, EN ISO 228-1
Service pressure
16 bar
Differential pressure for opening and closing
At least 0.5 bar
Duty cycle
100 % ED
Installation position
Any
Connection symbols
P = pressure connection
A = valve outlet
R = exhaust or drain outletSupply voltage (+/-10 %)n 24 V DC, 8 W
or optionally
– 230 V, 50 Hz, 15 VA, after pick-up 30 VA
Protection class
IP 65
Admissible ambient temperature
Max. 55 °C
Weight
Approx. 0.9 kg
Strainer Connection
G 1⁄2, EN ISO 228-1
Material
Housing MS 58
Filter cartridge 1.4571
Mesh width
0.5 mm
Weight
Approx. 0.3 kg