Technical data
Supply voltage
■ 24 V DC +/-20 %
Power consumption
■ max. 5 VA
Current input
■ max. 0.3 A
Required external fuse
■ 0.5 A M
Input/output
■ Interface for CAN bus to ISO 11898, CANopen, insulated
Inputs NRR 2-61
■ 1 x analogue input IN 2, 4 – 20 mA (feedwater owrate) – (option)
■ 1 x analogue input IN 3, 4 – 20 mA (steam owrate) – (option)
Outputs of MIN/MAX contacts/pump enable
■ 4 x volt-free relay contacts (changeover relays), contact material AgNi0.15, AgSnO2
Con gurable as:
◆ 2 x MIN/2 x MAX water level alarm.Alternatively:
◆ 1 x MIN/1 x MAX water level alarm.
◆ 2 x pump enable (ON/OFF) with actuation of a
frequency-controlled pump
■ Maximum switching current – 8 A at 250 V AC/ 30 V DC – cos φ = 1
Inductive loads must have interference suppression (RC combination) as per the manufacturer’s speci cation
Switch-off delay of MIN/MAX output relays
■ Factory default setting 3 seconds
Analogue output
■ 1 x actual value output OUT 1: 4 – 20 mA, e.g. for an actual value display
■ 1 x analogue output OUT 2: 4 – 20 mA, control point Yw■ Max. load resistance 500 W
Indicators and controls
■ 1 x multicolour LED (orange, green, red)
◆ orange = power up◆ green = running◆ red = malfunction
■ 1 x 4-pole code switch for setting the controller group and baud rate
Protection class
■ II double insulated
IP rating to EN 60529
■ Housing: IP 40
■ Terminal strip: IP 20
Electrical safety
■ Degree of contamination 2 for installation in control cabinet with protection rating IP 54, fully insulated